Fire Rating Requirements for Plenum Cables in Sacramento Buildings: What You Need to Know

When installing low-voltage or network cabling in Sacramento in modern commercial or institutional buildings around Sacramento, one of the most critical compliance challenges is ensuring that plenum-rated cables meet applicable fire rating requirements. Because plenum spaces carry recirculated air, the consequences of flame or smoke propagation are much more serious than in non-air spaces.

1. What Is a Plenum Space & Why It Matters

Definition of a plenum space

  • A plenum is an enclosed space used for air circulation—typically the return air return path or mixing air path in HVAC systems (for example, above a drop ceiling or under a raised floor).
  • Because a plenum space actively carries air, it behaves essentially like a duct: any combustion or smoke in that space can be rapidly distributed through the building’s ventilation network.
  • In older construction, drop-ceiling voids or raised floor cavities were often used as part of the building’s mechanical air path. Over time, many jurisdictions tightened regulation of such use to prevent hazard. ICC Digital Codes+3Wikipedia+3Sewell Direct+3

Why plenum spaces are high risk

  • They contain abundant oxygen and connect to multiple rooms, so even a small fire can spread fast.
  • Smoke, toxic gases, or heat from a burning cable can degrade visibility, hamper evacuation, and endanger occupants.
  • Thus, any cable installed in a plenum (unless fully enclosed in rated conduit) must have stringent flame and smoke performance characteristics.

As stated in industry overviews, “any cables installed in a plenum space must be plenum rated” to minimize flame propagation and smoke production. Waveform+2Sewell Direct+2


2. Understanding “Plenum Cable” and Its Fire Rating Fundamentals

What does “plenum rated” mean?

  • “Plenum cable” is cable whose jacket and insulation materials have been tested and listed for use in air-handling spaces.
  • The cable typically uses special fire-retardant materials (e.g. low-smoke PVC, FEP, fluoropolymers) that resist flame spread and produce less visible smoke. Sewell Direct+4Wikipedia+4datapro.net+4
  • Because of those materials and the test listing, plenum cable is more expensive than general-purpose cable (CM, CMR, CMP etc.). Wikipedia+2Sewell Direct+2

Cable rating nomenclature

Some common rating labels and their meaning include:

  • CMP (Communications, Plenum) — The designation for cables suitable for use in plenum spaces under NEC/UL standards.
  • CMR (Communications, Riser) — For vertical shafts; cannot be used where air handling is present.
  • CM, CMR, CMP, CMG, CMX, etc. — Other common cable classes used in networking and telecomm infrastructure, each with different fire performance expectations. Electrical License Renewal+2Sewell Direct+2
  • OFNP / OFCP — Optical fiber non-conductive / conductive, plenum versions. Wikipedia+2Wikipedia+2

Important caveat: Having a “plenum rating” does not mean the cable has a 1-hour or 2-hour fire resistance rating. The plenum rating speaks mainly to flame spread and smoke characteristics under standard test conditions, not necessarily sustained fire resistance. ElectroPro Insights+2Electrical License Renewal+2


3. National Code & Test Standards Governing Plenum Cable Fire Performance

NEC / NFPA framework

NEC Article 300.22 — Environmental Air (Plenums)

  • NEC Section 300.22 governs “Other Spaces Used for Environmental Air (Plenums).” Cable exposed in plenum spaces must be either metal-jacketed or listed for use in plenums (i.e. plenum rated). Electrical License Renewal+1
  • Specifically, 300.22(C)(1) permits factory-assembled multiconductor control or power cables only if they are listed for use within an air-handling space (plenum). Electrical License Renewal

NFPA 90A

  • NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, regulates the materials used in duct and plenum systems. Any cable placed in a plenum must satisfy the material performance criteria set by NFPA 90A. Wikipedia+2NFPA+2
  • NFPA 262 is referenced by NFPA 90A as the test method to evaluate flame travel and smoke. NFPA+2Wikipedia+2

NFPA 262 (Standard Method of Test for Flame Travel and Smoke)

Fire-resistive (Circuit Integrity) cables


4. California & Sacramento Jurisdiction — Local Adoption & Permitting

California code adoption

  • California uses Title 24, which includes California’s versions of the California Building Code (CBC), California Electrical Code (CEC), and California Fire Code (CFC). Wikipedia+1
  • Sacramento County has adopted the 2022 California Fire Code (CFC) as one of its fire prevention ordinances. eCode360+1
  • The county code indicates that the 2022 CFC is controlling within Sacramento County, except where local fire districts override. eCode360+1

Sacramento city electrical / low-voltage rules

  • In the City of Sacramento’s municipal code (Article XIII, Electrical Requirements), there is a clause that states: “All wiring used for life safety and fire alarm systems of high-rise buildings shall be installed in approved metal raceways. No other conductors shall be …” (i.e. indicates stricter rules for life-safety systems). American Legal Publishing
  • On low-voltage / cabling side, a local low-voltage trade website notes: “Plenum-rated cabling (CMP): Required in air-handling spaces for fire safety compliance.” Sac Low Voltage Techs
  • Thus, any project in Sacramento involving cabling above ceilings, below raised floors, or in HVAC return paths must use plenum rated (CMP / equivalent) unless fully enclosed in rated conduit.

Emergency Responder Radio (ERRS) rules — specific to Sacramento

  • Sacramento’s ERRS specification document requires 1- or 2-hour fire-rated circuit integrity (CI) cable in exit stairways or ramp enclosures, depending on building fire rating. cityofsacramento.gov
  • It also requires that fire-resistive cable systems installed outside the fire-rated rooms comply with NFPA 70 Article 728 (Fire-Resistive Cable Systems). cityofsacramento.gov

Local enforcement and inspections

  • Projects must submit plans to the Sacramento Building & Safety Division and obtain inspections verifying compliance with Title 24, fire code, and electrical code. Sac Low Voltage Techs
  • Fire prevention and code enforcement districts within Sacramento enforce the adopted CFC and relevant building/fire code amendments. eCode360

5. Specific Fire Rating Metrics & Performance Requirements

This section drills into how you measure compliance and what thresholds must be met.

Flame spread & smoke (NFPA 262 / UL 910)

  • The fundamental test for plenum cables is NFPA 262, which characterizes flame propagation and smoke. Some equivalent tests may be UL 910 (UL test for flame and smoke for plenum cables).
  • Key metrics:
     • Peak optical density ≤ 0.50
     • Average optical density ≤ 0.15
     • Flame spread distance ≤ 5 feet
  • Cable listings must show that the product has passed and is labeled for plenum use. Electrical License Renewal+2NFPA+2

Circuit integrity (CI) rating

  • Certain systems require that cable maintain operation while exposed to fire for a specified duration (e.g. 1 hour, 2 hours). These are more stringent than standard plenum ratings. CSE Magazine+3oliverfps.com+3cityofsacramento.gov+3
  • The cables intended for this purpose are tested under fire resistance standards (e.g. UL 2196) and must be listed as part of a fire-rated cable system (including supporting conduit, junction boxes, splices, etc.). cityofsacramento.gov+1
  • Example: the Sacramento ERRS spec states that when an exit stair or ramp enclosure has a 2-hour fire resistance rating, the riser cables must use 2-hour CI cable. cityofsacramento.gov

Derating and use in ducts

  • Under NFPA 90A and related code, the installation of plenum wiring in ducts is restricted. NFPA 90A generally allows only limited wiring length within ducts unless directly associated with the air distribution system (often limited to 4 feet). Cabling Install
  • Further, unlimited plenum cable lengths may conflict with NFPA 90A’s restriction, so designers must carefully interpret how NEC, NFPA, and local interpretations interact. Cabling Install+1

Certification, listing, labeling

  • The cable must be UL-listed (or equivalent) for plenum use. The product specification should show its listing designation (e.g. “CMP, UL listed, meets NFPA 262”).
  • All components—connectors, couplings, junction boxes—if exposed in plenum space, should also have compatible ratings or be enclosed in rated enclosures.
  • Installation must follow manufacturer’s instructions and listing documentation — deviating can void certification or code compliance.

6. Additional Constraints: Fire Alarm, Emergency Systems & Special Cases

Some systems have stricter fire rating requirements beyond basic plenum cable.

Fire alarm and life safety circuits

Emergency Responder Radio Systems (ERRS) / DAS / BDA

  • These systems, required in many jurisdictions including Sacramento, must use cabling with fire-resistive circuit integrity ratings. cityofsacramento.gov
  • The spec typically mandates 1- or 2-hour CI rated cable depending on the building’s fire rating and usage. cityofsacramento.gov
  • These cables must be installed in accordance with NFPA 70, Article 728 (Fire-Resistive Cable Systems). cityofsacramento.gov

Other special installations

  • If cables must cross fire barriers (walls, floor assemblies, rated shafts), they must pass through firestopping systems rated equal to or better than the barrier. CSE Magazine+2oliverfps.com+2
  • Mineral-insulated (MI or MICC) cables, which are inherently fire-resistant, may be allowed in some scenarios. These use inorganic insulation and metal sheathing and are less reliant on organic polymer performance. Wikipedia

7. Best Practices & Common Mistakes

Here’s a practical list of tips and pitfalls based on field experience and code commentary.

Best practices

  • Always use plenum-rated (CMP / equivalent) cable when you expect it to pass through any portion of air-handling or return-air systems unless entirely enclosed in rated conduit.
  • Maintain documentation of cable listings and tests (e.g. UL/ETL report sheets) for inspection and future reference.
  • Use full fire-rated junction boxes, couplings, and connectors in exposed plenum spaces.
  • Avoid running non-rated cables “just a short distance” through a plenum—inspectors often reject such partial compliance attempts.
  • Stay within maximum allowed lengths of cable in ducts, especially those associated with the HVAC system (e.g. the 4 ft limit) under NFPA 90A. Cabling Install
  • Use cable trays or supports rated or listed for the cable if in plenum paths; follow manufacturer’s spacing, support, and bend radius guidance.
  • Firestop and seal penetrations with materials approved for the rating of the barrier.
  • Perform regular inspections and maintenance checks, particularly in critical life-safety systems that rely on fire-rated cables.

Common mistakes & misconceptions

  • Assuming plenum rating = fire rating: As noted earlier, a plenum rating does not guarantee a 1- or 2-hour circuit integrity rating. ElectroPro Insights
  • Substituting riser-rated (CMR) cable in plenum spaces. This is typically non-compliant and often rejected in inspection. Delco Cables+1
  • Ignoring the listing of accessories and terminations – only the cable is rated, but if connectors, couplings, or boxes are not rated compatibly, the installation may fail.
  • Poor documentation or lacking a listing sheet – inspectors often require the specific cable’s listing sheet.
  • Cables too close to hot surfaces (ducts, HVAC units, etc.) – even plenum-rated cables have temperature limitations and must be kept away from extreme heat sources per manufacturer guidelines.
  • Mixing incompatible fire-stop systems – using materials not rated for the specific barrier can compromise the assembly’s integrity.

8. Sample Compliance Checklist for Sacramento Projects

Here’s a practical checklist you (or your inspector) can run through during design or installation:

ItemCheck / SourceNotes
Cable is plenum-rated (CMP / equivalent)UL / ETL listing sheetConfirm it passes NFPA 262 or UL 910
Connectors, boxes, couplings are ratedListing documentationMust be compatible with exposed plenum
Cable path is truly in plenum or enclosedBIM, drawings, field verificationAvoid assumptions of “non-plenum”
Cable does not exceed allowed duct length (if in HVAC ducts)NFPA 90A / HVAC planUsually limited to about 4 ft
Fire alarm / emergency circuits use CI-rated cablesERRS spec, NFPA 70, Article 728, local rulesPer Sacramento ERRS, 1–2 hour CI cables may be required cityofsacramento.gov
Penetrations sealed with fire-stop system equal to barrier ratingFire-stop manufacturer spec, UL systemsCabling paths through walls, floors, shafts
Support and spacing follow manufacturer specsCable spec sheetAvoid excess bending or stress on jackets
Maintain installation and listing documentationProject files, as-built schematicsInspectors will often request during final inspection
Coordination with mechanical / HVAC tradesDuring planningEnsure cable routing doesn’t conflict, stay clear of hot ducts
Plan submittal includes fire rating sectionPermit drawingsShow notes about plenum and CI cable where applicable

You can adapt this to your project forms or inspection checklists.


9. Conclusion & Key Takeaways

  • Plenum cable fire rating is essential in Sacramento and California, especially for any wiring passing through air-handling or return spaces.
  • The core test reference is NFPA 262, which governs flame spread and smoke density.
  • Plenum rating (e.g. CMP) is distinct from circuit integrity / fire-resistive rating (1- or 2-hour).
  • Sacramento has specific rules, particularly for life safety systems and ERRS, which may mandate CI-rated cables.
  • Always use only rated accessories, proper installation, fire sealing, and thorough documentation to ensure compliance.
  • Use the checklist above in your design, installation, and inspection cycles.

With this article, you’ll be well positioned to write a version tailored to your audience (engineers, contractors, building owners) or to accompany permit submittals and project documentation.